Customization: | Available |
---|---|
Application: | Power, Electronic, Instrument, Lighting, Rectifier, Audio |
Phase: | Three |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Applying Ambient Conditions:
1.Installation Height : the atitude should not exceed 1000m
2. Ambient temperature: -30ºC-+40ºC
3.Installation environment inclination of installation lace<3, no obvious dirt and corrosive or flammable gas
4.Notes: If the operating conditions exceed the normal conditions, please contact our technical department
Rated capacity (kVA) | Voltage combination | Vector group | No - load loss (W) of SCB10 | No - load loss (W) of SCB11 | No - load loss (W) of SCB12 | Load loss (W) | No - load current (%) | Short - circuit impedance (%) | |||
High voltage (kV) | High voltage tapping range (%) | Low voltage (kV) | F(120°C) | H(145°C) | |||||||
30 | 6,6.3,6.6,10,10.5,11 | ±5 or ±2×2.5 | 0.4 | Dyn11 or Yyn0 | 190 | 170 | 150 | 710 | 760 | 2.3 | 4 |
50 | 270 | 240 | 215 | 1000 | 1070 | 2.2 | |||||
80 | 370 | 330 | 295 | 1380 | 1480 | 1.7 | |||||
100 | 400 | 350 | 320 | 1570 | 1680 | 1.7 | |||||
125 | 470 | 420 | 375 | 1850 | 1980 | 1.5 | |||||
160 | 540 | 480 | 430 | 2130 | 2280 | 1.5 | |||||
200 | 620 | 550 | 495 | 2530 | 2710 | 1.3 | |||||
250 | 720 | 640 | 575 | 2760 | 2960 | 1.3 | |||||
315 | 880 | 780 | 705 | 3470 | 3720 | 1.1 | |||||
400 | 980 | 860 | 785 | 3990 | 4280 | 1.1 | |||||
500 | 1160 | 1030 | 930 | 4880 | 5230 | 1.1 | |||||
630 | 1340 | 1190 | 1070 | 5880 | 6290 | 0.9 | |||||
630 | 1300 | 1150 | 1040 | 5960 | 6390 | 0.9 | 6 | ||||
800 | 1520 | 1350 | 1215 | 6960 | 7460 | 0.9 | |||||
1000 | 1770 | 1580 | 1415 | 8130 | 8710 | 0.9 | |||||
1250 | 2090 | 1860 | 1670 | 9690 | 10380 | 0.9 | |||||
1600 | 2450 | 2170 | 1960 | 11730 | 12550 | 0.9 | |||||
2000 | 3050 | 2710 | 2440 | 14450 | 15470 | 0.7 | |||||
2500 | 3600 | 3190 | 2880 | 17170 | 18380 | 0.7 | |||||
3150 | 4280 | 3850 | 3460 | 20540 | 21990 | 0.8 |